Abstract:Aiming at the huge system composition and complex operation of a continuous wind tunnel, a method of combining fault tree analysis (FTA) and failure mode and effect analysis (FMEA) is proposed. The fault tree model of a continuous wind tunnel is established by taking the operation fault of the wind tunnel as the top event, and the important fault bottom events leading to the top event are summarized from top to bottom. The FMEA is used to analyze and evaluate the bottom events, and identify all the failure modes that affect the safety of wind tunnel operation. On this basis, a set of wind tunnel safety interlocking system based on distributed PLC is developed. Each process subsystem of the wind tunnel monitors the status of the associated fault events, and the safety interlocking system is responsible for collecting the fault identification results of all subsystems and the key wind tunnel status information, and uniformly dispatching to realize the safety interlocking shutdown of the whole wind tunnel when a fault occurs. The test results show that the safety interlocking system can find the faults and hidden dangers in the operation of the wind tunnel in time, and implement the perfect emergency shutdown interlocking logic, which can effectively guarantee the safety of personnel and equipment, and provide reliable decision-making assistance for operators to troubleshoot.